Section available in PDF format. Click here to view... |
Three Phase Relays - We design and manufacture a number of multi function Three Phase Relays:
phase monitor; 3 phase relay; phase failure; phase sequence; phase sequence relay; phase failure relay; 3 phase under voltage; phase loss; three phase monitor; 3 phase monitor; three phase relay; 3 phase over voltage; over and under voltage relay.
These Three Phase Relays are supplied with various mountings:- The M1 series either DIN rail or surface mounting
- The M3 series either DIN rail or surface mounting
- The M5 series either DIN rail or surface mounting
- The B1 series with 11 pin mounting
- The B8 series with 8 pin mounting
- The 45 series for DIN rail mounting
- The 70 series for either surface or DIN rail mounting
See below for our complete range of Three Phase Relay products.
| | Display: [All | New | Home] Scroll to right to see all products. Click in title area to view PDF file if available. |
| MX & M1 Series DIN Rail & Surface Mtg |
Click to enlarge
DIMS: (mm) H.89 W.17.5 D.59
|
| Type No |
 |
MXPRC-S |
 |
|
 |
MXPRC |
 |
|
 |
MXPRT |
 |
|
 |
MXPRF |
 |
|
| Description |
Three Phase Under & Over Voltage Relay |
Three Phase Under & Over Voltage Relay |
Three Phase Under Voltage/Sequence/Loss Relay |
Three Phase Sequence/Loss Relay |
| Function |
Voltage (True RMS) |
Voltage (True RMS) |
Voltage (True RMS) |
Voltage (True RMS) |
| Under / Over Voltage |
Under & Over |
Under & Over |
Under |
Under (Fixed) |
| Adjustable Trip Level |
Yes |
Yes |
Yes |
No |
| Phase Loss (Failure) |
Yes |
Yes |
Yes |
Yes |
| Neutral Loss |
No |
No |
No |
No |
| Phase Sequence (Rotation) |
Yes |
No |
Yes |
Yes |
| Phase Asymmetry |
No |
No |
No |
No |
| Time Delay (from fault) |
0.2 - 10S |
0.2 - 10S |
0.2 - 10S |
~100mS |
| Output |
1 x SPDT Relay |
1 x SPDT Relay |
1 x SPDT Relay |
1 x SPDT Relay |
| Output Rating |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
| Integral Transformer |
No |
No |
No |
No |
| Supply Voltage Un/U |
Un: 110, 208, 220, 380, 400, 415VAC |
Un: 110, 208, 220, 380, 400, 415VAC |
U: 77 - 143, 161 - 300, 280 - 520VAC |
U: 77 - 143, 161 - 300, 280 - 520VAC |
| |
- |
- |
- |
- |
| |
- |
- |
- |
- |
| Monitoring Range |
Monitors own supply |
Monitors own supply |
Monitors own supply |
Monitors own supply |
|
| M3 Series - Key Range With DPDT Output DIN Rail & Surface Mtg |
Click to enlarge
DIMS: (mm) H.89 W.35 D.59
|
| Type No |
 |
M3PRT-2 |
 |
|
 |
M3PRT-2-4W |
 |
|
| Description |
Three Phase Under Voltage/Sequence/Loss Relay |
Three Phase Under Voltage/Sequence/Loss Relay |
| Function |
Voltage |
Voltage |
| Under / Over Voltage |
Under |
Under |
| Adjustable Trip Level |
Yes |
Yes |
| Phase Loss (Failure) |
Yes |
Yes |
| Neutral Loss |
No |
Yes |
| Phase Sequence (Rotation) |
Yes |
Yes |
| Phase Asymmetry |
No |
No |
| Time Delay (from fault) |
0.2 - 10S (adjustable) |
0.2 - 10S (adjustable) |
| Output |
DPDT Relay |
DPDT Relay |
| Output Rating |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
| Integral Transformer |
No |
No |
| Supply Voltage Un/U |
U: 280 - 520V phase to phase |
U: 161 - 300V phase to neutral |
| |
- |
- |
| |
- |
- |
| Monitoring Range |
Monitors own supply |
Monitors own supply |
|
| M3 Series - High Voltage And Specialist Range DIN Rail & Surface Mtg |
Click to enlarge
DIMS: (mm) H.89 W.35 D.59
|
| Type No |
 |
M3PRT-600V |
 |
|
 |
M3PRT-4W-346V |
 |
|
 |
M3PRC-S-4W-332V-346V |
 |
|
| Description |
Three Phase Under Voltage/Sequence/Loss Relay |
Three Phase Under Voltage/Sequence/Loss Relay |
Three Phase Under & Over Voltage/Loss/Sequence Relay |
| Function |
Voltage |
Voltage |
Voltage |
| Under / Over Voltage |
Under |
Under |
Under & Over |
| Adjustable Trip Level |
Yes |
Yes |
Yes |
| Phase Loss (Failure) |
Yes |
Yes |
Yes |
| Neutral Loss |
No |
Yes |
Yes |
| Phase Sequence (Rotation) |
Yes |
Yes |
Yes |
| Phase Asymmetry |
No |
No |
No |
| Time Delay (from fault) |
0.2 - 10S (adjustable) |
0.2 - 10S (adjustable) |
0.2 - 10S (adjustable) |
| Output |
SPDT Relay |
SPDT Relay |
DPDT Relay |
| Output Rating |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
| Integral Transformer |
No |
No |
No |
| Supply Voltage Un/U |
U: 336 - 624V phase to phase |
U: 194 - 360V phase to neutral |
Un: 332, 346V phase to neutral |
| |
- |
- |
(based on 575V and 600V |
| |
- |
- |
phase to phase) |
| Monitoring Range |
Monitors own supply |
Monitors own supply |
Monitors own supply |
|
| B8 Series 8 Pin Plug-In |
Click to enlarge
DIMS: (mm) H.80 W.40 D.92
|
| Type No |
 |
B8PMU |
 |
|
 |
B8PMC |
 |
|
| Description |
Three Phase Under Voltage/Sequence/Loss Relay |
Three Phase Under & Over Voltage Relay |
| Function |
Voltage |
Voltage |
| Under / Over Voltage |
Under |
Under & Over |
| Adjustable Trip Level |
Yes |
Yes |
| Phase Loss (Failure) |
Yes |
Yes |
| Neutral Loss |
No |
No |
| Phase Sequence (Rotation) |
Yes |
Yes |
| Phase Asymmetry |
No |
No |
| Time Delay (from fault) |
0.2 - 10S |
0.2 - 10S |
| Output |
1 x SPDT Relay (US Pin-Out) |
1 x SPDT Relay (US Pin-Out) |
| Output Rating |
10A @ 250VAC |
10A @ 250VAC |
| Integral Transformer |
No |
No |
| Supply Voltage Un/U |
84-156VAC, 154-286VAC |
120, 208, 240, 460, 480VAC |
| |
242-450VAC, 308-572VAC |
- |
| |
- |
- |
| Monitoring Range |
Monitors own supply |
Monitors own supply |
|
|
|